Flat cable FE180/E90 3G6² HF OR
Article number: 48550OR
Price on demand
Flat cable Woertz FE180/E90 0.6/1.0kV, 3x6mm², halogen-free, HFFR,
orange, LNPE, reaction to fire class: B2ca s1a d0 a1, rodent repellent
| Base Unit | Meter |
| availability | Delivery according to agreement |
| Weight | 350 g |
| Construction | 3x6 mm² |
| Halogen free | Yes |
| International designation | N1ZZ1H2-U |
| Reaction to fire classification | B2ca s1a d0 a1 |
| Fire behavior | Cables with non-critical behavior (according to VKF 14-15) |
| Sheath color | Orange |
| Rodent protection | rodent repellent |
Tender text
Flat cable FE180/E90 3G6² HF OR (48550OR): Flat cable Woertz FE180/E90 0.6/1.0kV, 3x6mm², halogen-free, HFFR,
orange, LNPE, reaction to fire class: B2ca s1a d0 a1, rodent repellent
Copy
| Construction | 3x6 mm² |
| Halogen free | Yes |
| Cable type | Fire safety flat cable |
| International designation | N1ZZ1H2-U |
| Reaction to fire classification | B2ca s1a d0 a1 |
| Fire behavior | Cables with non-critical behavior (according to VKF 14-15) |
| Cross section (mm²) | 6 mm² |
| Copper conductor | Wire KL1 EN60228 |
| Conductor resistance (ohm/km) | 3,08 ohm/km |
| cores insulation | Flame retardant, high temperature resistant |
| Cores colors | brown,green/yellow,blue |
| Sheat insulation | Polyolefin flame retardant |
| Sheath color | Orange |
| Rodent protection | rodent repellent |
| Longitudinal watertightness | < 1 m/14 days EN60794-1-2-F5B |
| Operating Temperature | -25 till 90 °C |
| Installation temperature min. | 5 °C |
| Nominal voltage (VAC) | 600/1000 VAC |
| Test voltage | 4 kV/50Hz |
| Fire load (kWh/m) | 0,91 |
| Halogen free acc. to | IEC/EN60754-1/2 |
| Flame retardant according to | IEC/EN60332-1-2 |
| Minimal smoke emision acc. to | IEC/EN 61034-2 |
| Insulation integrity | FE180 (IEC 60331) / PH120 (EN50200) |
This product is a member of the following product systems
3011
Woertz fire safety system FE180 E30/E90 3G6 mm² for supplying power to safety-relevant elements such as emergency and escape route lighting, smoke extraction systems or fire department elevators.