Box FC E90 3G2.5 with fuse

Box FC E90 3G2.5 with fuse

Article number: 48253/SI
Price on demand
Fire safety box with fuse adapter IP66/68 for flat cable FE180 E90 3G2.5 mm² incl. 3 x cable gland M20x1.5, with a clamping range of Ø 6-8 mm, Ø 8-11 mm and Ø 11-15 mm respectively

Project-specific design on request see document/G00'299
Base Unit Piece
Dimensions length x width x height (mm) 247x50x49 mm
availability Delivery according to agreement
Number of poles 3 pole
Weight (g) 447 g
Color orange
Tender text
Box FC E90 3G2.5 with fuse (48253/SI):
Copy
Files
Instruction manual
Assembly video
Declaration of Conformity
Instruction manual
Characteristics
Base Unit Piece
availability Delivery according to agreement
group 170000
country of origin CH
Customs tariff number 8536.9080
Weight (g) 447 g
Color orange
Technical data
Dimensions length x width x height (mm) 247x50x49 mm
Dimensions length x width x height (inch) 9.72x1.97x1.93 inch
Degree of protection IP66/IP68 (2m,30min)
Metal parts Metal parts:V4A / Contacting : Cu alloy
Flat cable contacting type Piercing contact (screw) EN 60998-2-3
Number of poles 3 pole
Contacting type Screw terminal
Connection conductor (mm²) 3x2.5 mm²
Thread cable gland mit 3 Kabelverschraubungen M20x1.5 (IP68) D= 6.0 mm - 15.0 mm
Cable gland (mm) 6.0- 15.0 mm
Rated current heavy current part (A) 16 A
Rated voltage heavy current part (V) 250 V
Fuse Single-phase (For ceramic fuse 5x20 mm)
Operating Temperature (°C) -15 to 85 °C
Installation temperature min. (°C) 5 °C
Function maintenance E30/E90 (DIN 4102-12)
Plastic parts Halogen-free
Material slider/bottom part Polyamide, orange
Material housing Polyamide, orange
Material hood Polyamide, orange
Fire load (KWh) 1,38 kWh

Product accessories

Retaining plate to connection box 48253/48453
Article number 48254
Base Unit Piece
availability Delivery according to agreement
Weight (g) 78
Price on demand

This product is a member of the following product systems

3000
Woertz Fire Safety System FE180 E30/E90 3G2.5 mm² for power supply of safety-relevant elements, such as emergency and escape route lighting, smoke extraction systems or fire department elevators.