Box FC E90 5G2.5 junction M20 D:8-11

Box FC E90 5G2.5 junction M20 D:8-11

Article number: 48353/02
Price on demand
Fire safety boxes IP66/IP68, incl. cable gland, 2-screw contacting, for stripping-free feeding and branching, with screw connection for heavy current 5P2.52 , longitudinal, thread M20x1.5
Base Unit Piece
Dimensions length x width x height (mm) 185x65x70 mm
availability Delivery according to agreement
Number of poles 5 pole
Weight (g) 775,7 g
Color orange
Tender text
Box FC E90 5G2.5 junction M20 D:8-11 (48353/02):
Copy
Files
Assembly video
Declaration of Conformity
Instruction manual
Characteristics
Base Unit Piece
availability Delivery according to agreement
EAN Code 7611718269899
group 170000
Packaging unit 1
country of origin CH
Customs tariff number 8536.9080
Weight (g) 775,7 g
Color orange
Technical data
Dimensions length x width x height (mm) 185x65x70 mm
Dimensions length x width x height (inch) 7.28x2.56x2.76 inch
Degree of protection IP66/IP68 (2m,30min)
Metal parts Metal parts:V4A / Contacting : Cu alloy
Flat cable contacting type Piercing contact (screw) EN 60998-2-3
Number of poles 5 pole
Contacting type Screw terminal
Connection conductor (mm²) 5x2,5 mm²
Thread cable gland mit Kabelverschraubung M20x1.5 (IP68) D= 8.0 mm - 11.0 mm
Cable gland (mm) 8.0 -11.0 mm
Rated current heavy current part (A) 24 (2,5 mm²) A
Rated voltage heavy current part (V) 690 V
Operating Temperature (°C) -15 to 85 °C
Installation temperature min. (°C) 5 °C
Function maintenance E30/E90 (DIN 4102-12)
Plastic parts Halogen-free
Material slider/bottom part Polyamide, orange
Material housing Polyamide, orange
Material hood Polyamide, orange
Fire load (KWh) 1,91 kWh

Product accessories

Retaining plate for junction box 48353-55/48653-55/48753-55
Article number 48354
Base Unit Piece
availability Delivery according to agreement
Weight (g) 131
Price on demand

This product is a member of the following product systems

3020
Woertz Fire Safety System FE180 E30/E90 5G2.5 mm² for power supply of safety-relevant elements, such as emergency and escape route lighting, smoke extraction systems or fire department elevators.