Pre-wired connection C3-M 5G1.5 5m HF
Article number: 49345/5M/C3
 
	ELDAS® number: 157513817
 
Price on demand 
		Pre-wired connector, plug 5-poles code 3 with 5 m cable 5G1.5 mm ² with free end, conductor compressed, 16 A, 250/400 V, halogen free, behaviour to fire classification Cca
| Base Unit | Piece | 
| Dimensions length x width x height (mm) | 5000 x 52.3 x 13.7 mm | 
| availability | available from stock | 
| Number of poles | 5 pole | 
| Weight | 605 | 
| Color | Pebble gray | 
| Coding plug connection | Code 3 | 
| Cable length (m) | 5 m | 
| Halogen free | Yes | 
| International designation | N05Z1Z1-F | 
| Reaction to fire classification | Cca s1 d0 a1 | 
| Sheath color | Black | 
	Tender text
	
		
Pre-wired connection C3-M 5G1.5 5m HF (49345/5M/C3): Pre-wired connector, plug 5-poles code 3 with 5 m cable 5G1.5 mm ² with free end, conductor compressed, 16 A, 250/400 V, halogen free, behaviour to fire classification Cca
		
			Copy
		
	| Dimensions length x width x height (mm) | 5000 x 52.3 x 13.7 mm | 
| Dimensions length x width x height (inch) | 197 x 2.06 x 0.54 inch | 
| Degree of protection | IP20, IP40 (Connected),IP68 (with sealing cover) | 
| Number of poles | 5 pole | 
| Material | polyamide | 
| Rated current heavy current part (A) | 16 A | 
| Rated voltage heavy current part (V) | 250/400 V | 
| Cable length (m) | 5 m | 
| Halogen free | Yes | 
| Cable type | Halogen free cables | 
| International designation | N05Z1Z1-F | 
| Reaction to fire classification | Cca s1 d0 a1 | 
| Cross section (mm²) | 1.5 mm² | 
| Copper conductor | Fine stranded KL5 EN60228 | 
| cores insulation | Flame retardant polyolefin | 
| Cores colors | brown,blue,green/yellow,black,gray | 
| Sheat insulation | Polyolefin flame retardant | 
| Sheath color | Black | 
| Minimum bending radius | 6xD | 
| Operating Temperature | -15 till 70 °C | 
| Installation temperature min. | 5 °C | 
| Test current heavy current part (kV) | 4 kV | 
| Halogen free acc. to | IEC/EN60754-1/2 | 
| Flame retardant according to | IEC/EN60332-1-2 | 
| Minimal smoke emision acc. to | IEC/EN 61034-2 | 
| Fire load (KWh) | 1.85 kWh | 